Item | Description |
---|---|
Input Voltage | 24~50VDC |
Overvoltage protection | 85VDC |
UnderVoltage protection | 15VDC |
OverHeat protection | 80°C (Temperature of Thermistor) |
Phase current (peak) | 1/1.5/2/2.5/3/3.5/4/4.5 A – 8 settable values |
Subdivision | 200~25600 Pulses / revolution, 15 subdivision levels in total |
Adaptable Motor | Nema 23 motors |
Input Signal | PLS (CW) - DIR (CCW) – FREE – Input voltage : 5~24VDC – Input current : 8mA@5VDC / 12mA@24VDC |
Control Mode | Pulse control : PLS + DIR – CW/CCW |
Output signal | ERR - open collector output – maximum current : 100mA |
Operation Indicator | Combination of RUN and ERR Led indicates different status |
Protection Circuit | Over voltage – Under voltage – Over current – Over heat |
Cooling method | Nature air cooling |
Operation environnement | Indoor - installed in the environnement free from direct sunlight – dust – corrosive gas – combustible gas – oil mist – steam and drip |
Operation humidity | <85%RH – non-condensing or water drops |
Operation temperature | 0°C~40°C |
Storage temperature | -20°C~70°C |
Ingress protection | IP20 |
Subdivision setting (Unit : Pulses/Rev.) | Current setting (Unit:A) | ||||||||
---|---|---|---|---|---|---|---|---|---|
SW1 | SW2 | SW3 | SW4=ON | SW4=OFF | SW6 | SW7 | SW8 | RMS | Peak |
ON | ON | ON | 200 | 1000 | ON | ON | ON | 3.2 | 4.5 |
OFF | ON | ON | 400 | 2000 | OFF | ON | ON | 2.8 | 4 |
ON | OFF | ON | 800 | 4000 | ON | OFF | ON | 2.5 | 3.5 |
OFF | OFF | ON | 1600 | 5000 | OFF | OFF | ON | 2.1 | 3 |
ON | ON | OFF | 3200 | 8000 | ON | ON | OFF | 1.8 | 2.5 |
OFF | ON | OFF | 6400 | 10000 | OFF | ON | OFF | 1.4 | 2.0 |
ON | OFF | OFF | 12800 | 20000 | ON | OFF | OFF | 1.1 | 1.5 |
OFF | OFF | OFF | 25600 | NA | OFF | OFF | OFF | 0.7 | 1.0 |
Function | DIP setting | Description |
---|---|---|
PLS + DIR | SW6 & SW7 = ON – Others OFF | Set DIP switches according to functions required when power OFF. Power On driver : RUN Led blinking is GREEN & ERR Led is RED. It means settings takes effect. Then Power OFF driver – reset subdivision and current for normal use |
CW/CCW | SW7 & SW8 = ON – Others OFF | |
Micro-Step smooth & dynamic filter disable | SW5 & SW6 = ON – Others OFF | |
Micro-Step smooth filter enable | SW5 & SW7 = ON – Others OFF | |
Micro-Step dynamic filter enable | SW5 & SW8 = ON – Others OFF | |
Test motor parameter upon power on disable | SW6 & SW7 & SW8 = ON – Others OFF | |
Test motor parameter upon power on enable | SW5 & SW6 & SW7 = ON – Others OFF | |
Test-running | SW6 & SW8 = ON – Others OFF | Motor running @80RPM |
Automatic half-current | SW5 = ON – Others OFF | Set SW5=ON to enable automatic half-current. Phase current will reduce to half of the set value after motor stops for 1.5s |